Acrel Low Voltage Smart Motor Protection Meter connect to PLC by RS485 Modbus, ARD2L-25/C, with LCD Acrel Brand Voltmeter and Digital Ammeter with Current PZ72L-DE DC Energy Meter Manufacturer EV Char Acrel AIM-M200 Insulation Monitor Device IEC approved used for hospital IT power supply system Acrel 220V 400A 4 Circuits AC Three Phase Kwh Meter Come With 12 Split Type CTs measuring kWh kVarh Acrel ADW300W/C three phase energy meter with 3 splict core CTs 100A , dia16mm , RS485 Modbus, (wifi Acrel DC Energy Meter AMC16-DETT 6-Way Measurement for Base Station
Detail

Overview

Essential details

Packaging & delivery

Product Discription


ADW300 Energy Meter

ADW300 energy meter is mainly used to measure three phase current ,voltage,power,kwh, harmonic in low-voltage network(<690v).


It is standard with 3 split core current transformers, 100A /400A/600A optional.


It has various communication methods. RS485-Modbus / 4G module in-built / WIFI module in-built/ Lora module in-built optional.



Function

Functional description

Display mode

LCD (Field form)


Electric energy
metering

Active power metering (positive and reverse); four quadrant reactive power

Electricity measurement

Voltage, current, power factor, frequency, active power, reactive power, apparent power


Harmonic function

Total harmonic content and fractional harmonic content (2-31 times)

Pulse output

Active Power Pulse Output

Three-phase unbalance

Voltage and current unbalance

Temperature measurement function

A, B, C, N four-way temperature measurement (Optional T)

Tiered pricing

Two sets of time tables, a year can be divided into four time zones, each set of time table can set 12 days, four rates (F1, F2, F3, F4 namely Sharp,peak,flat and valley).

DI /DO

4DI/2DO (Optional K)

Residual electricity

1-way Residual Electricity Measurement

LED instruction

Pulse and other indication

External CT

External open type CT (Optional W)




Communication

Infrared Communication

RS485 Interface (Optional C)

470MHZ Wireless Transmission (Optional LR)

GPRS Wireless Communication (Optional 2G)

NB-IOT Wireless Communication (Optional NB)

WIFI Wireless Communication (Optional WIFI)

Power Cut Upload

Save the report during the power cut, upload the data after powering on (Optional U)

Voltage input

Rated voltage

3×220/380V,3×380V,3×57.7/100V,3×100V

Reference frequency

50Hz

Power consumption

<10VA or 2W(A),<0.5VA(B,C)


Current input

Input current

3×1(6)A ,   3×20(100)A(ADW300W)

Start current

4‰Ib(1class)

Power consumption

<2VA


Measurement performance

Standard

GB/T17215.321-2008,GB/T17215.322-2008

Active energy accuracy

0.5S class

Temperature Accuracy

±2℃

pulse

pulse width

80±20ms

Impulse constant

6400imp/kWh



Communication


wireless

Transmission on 470MHz and maximum distance in open space is 1km

Infrared communication

The constant baud rate is 1200

Interface

RS485(A,B)

Connection mode

Shielded twisted pair conductors

Protocol

MODBUS-RTU,DL/T 645-07

Dimensions

Wiring


Report 0 Favorite 0 Comment 0
more>Related
KYN28-12 Medium voltage MV electrical Switch gear for power distribution High voltage energy saving panel with automatic power factor correction high voltage KYN28-12 Switchgear main electrical switch board for indoor substation equipment AC type surge protector SPD Surge Protective Device 100ka Intelligent Motor Protector intelligent Reactive power compensation controller automatic power factor controller