Cart
Cart

Acrel AIM-M200 Insulation Monitor Device IEC approved used for hospital IT power supply system

 
Price $1292.30
Pay on delivery Support
Comments 0
Hits 5493
Quantity
+-
stock1000Piece
 
Company integrity file
more>New
Acrel Low Voltage Smart Motor Protection Meter connect to PLC by RS485 Modbus, ARD2L-25/C, with LCD Acrel Low Voltage Smart Motor Protection Meter connect to PLC by RS485 Modbus, ARD2L-25/C, with LCD Acrel Brand Voltmeter and Digital Ammeter with Current PZ72L-DE DC Energy Meter Manufacturer EV Char Acrel AIM-M200 Insulation Monitor Device IEC approved used for hospital IT power supply system Acrel 220V 400A 4 Circuits AC Three Phase Kwh Meter Come With 12 Split Type CTs measuring kWh kVarh Acrel ADW300W/C three phase energy meter with 3 splict core CTs 100A , dia16mm , RS485 Modbus, (wifi

Overview

Essential details

  • Place of Origin:

  • Jiangsu, China

  • Brand Name:

  • Acrel

  • Model Number:

  • AIM-M200

  • Display Type:

  • Digital Only

  • Phase:

  • /

  • Operating Temperature:

  • -25℃~+65℃

  • Dimensions:

  • /

  • Powr supply for device:

  • DC 24 V

  • Power consumption:

  • 3 VA

  • Insulation resistance Monitor:

  • 10~999kΩ

  • Alarm of Insulation resistance:

  • 50~999kΩ

  • Reaction time:

  • 2S

  • Current Monitor:

  • 2.1~50A

  • Temperature Monitor:

  • -50℃~+200℃

  • DIgital output:

  • 2 relay ouput(not programmable)

  • Contact capacity:

  • 2A/30VDC or 2A/250VAC

  • Interface:

  • RS485*1, Modbus-RTU/ CAN

Packaging & delivery

  • Packaging Details

  • carton
  • Port

  • Shanghai
  • Picture Example:

  • package-img

  • Lead time:

  • Quantity(pieces)1 - 1011 - 3031 - 100>100
    Lead time (days)357To be negotiated

Technical parameters

Parameter

Value

Power Supply

DC 24V

Power consumption

3 VA

Insulation resistance Monitor

10~999kΩ

Alarm resistance

50~999kΩ

Reaction time

2S

Measureing voltage

<12 V

Current Monitor

2.1~50A

Alarm value

5~50A

Accuracy

5%

Temperature Monitor

PT100

Monitor range

-50℃~+200℃

Alarm value

0℃~+200℃

Alarm output

2 relay(not programmable)

Contact capacity

AC 250V/3A, DC 30V/3A

Communication

RS485, Modbus RTU; CAN

Working temperature

-20℃~+55℃

Notes:

IEC certificate

Application


Report 0 Favorite 0
more>Related
Acrel Electric Temperature ATE400 Temperature Measurement Sensor Acrel Low Voltage Smart Motor Protection Meter connect to PLC by RS485 Modbus, ARD2L-25/C, with LCD Acrel Low Voltage Smart Motor Protection Meter connect to PLC by RS485 Modbus, ARD2L-25/C, with LCD Acrel Brand Voltmeter and Digital Ammeter with Current PZ72L-DE DC Energy Meter Manufacturer EV Char Acrel AIM-M200 Insulation Monitor Device IEC approved used for hospital IT power supply system Acrel 220V 400A 4 Circuits AC Three Phase Kwh Meter Come With 12 Split Type CTs measuring kWh kVarh